Permit: T01CM01188
Permit Details
Apply Date:
03/12/2001
Applicant:
SONORA EXPEDITING
Description:
TI:OFFICE
Contractors:
- RALLY CONSTRUCTION COMPANY INC ,
Permit Reviews
Permit Number - T01CM01188
Permit Status: C of o
Permit Description: TI:OFFICE
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
03/12/2001 | COMMERCIAL TI | 04/17/2001 | COMPLETED |
04/17/2001 | RESUBMITTAL | 05/04/2001 | COMPLETED |
04/17/2001 | SITE | 05/04/2001 | COMPLETED |
05/04/2001 | OTHER | 05/04/2001 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T01CM01188
Permit Status: C of o
Permit Description: TI:OFFICE
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
03/12/2001 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: C of o
Permit Number: T01CM01188
Permit Description: TI:OFFICE
Total Completed Inspections - 21
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/15/2001 | SHEET ROCK NAILING | DWITT | Approved | IVRS - Inspection 0000*SHT. ROCK |
05/22/2001 | PLUMBING - ROUGH, SOIL | FMCCLURE | Approved | IVRS - Inspection 0000* |
06/26/2001 | ELECTRIC - INTERMEDIATE | RMAJUTA | Approved | IVRS - Inspection 0000*ELECT RM 4-3" EMTS ABOVE CEILING & WALLS & CEILING OK TO COVER HALL ENTRY CEILING OK TO COVER |
06/28/2001 | MECHANICAL - ABOVE CEILING | JMILITEL | Approved | IVRS - Inspection 0000*PROVIDE AN ACCESS DOOR TO FIRE DAMPER ON HALLWAY WALL. |
06/28/2001 | ELECTRIC - UNDERGROUND | RMAJUTA | Approved | IVRS - Inspection 0000*1.) 4" PVC'S TEP POLE TO TRANS 4 3" PVC'S TRANS TO BLDG 2 2" PVC'S BLDG TO GEN 3.) 1 1/4 PVC BLDG TO GEN 4.) 3/4 PVC' BLDG TO GEN 2 GROUND RODS W/3/0 CU. ALL OK TO COVER |
06/29/2001 | FRAMING | DWITT | Approved | IVRS - Inspection 0000*BATTERY WALLS STOP @ CEIL. PLEASE HAVE ARCHITECT REVIEW THE NOTE RE: RAISING THE WALL TO DECK OK LID. |
07/16/2001 | BOILER FINAL | RLOHRMAN | Approved | IVRS - Inspection 0000* |
07/16/2001 | BOILER - EXPANSION TANK | RLOHRMAN | Approved | IVRS - Inspection 0000* |
07/16/2001 | BOILER UNFIRED PRESSURE VESSEL | RLOHRMAN | Approved | IVRS - Inspection 0000*HANSON 2001 NB178545 WP125PSI S#401496 |
09/21/2001 | REINFORCED MASONRY PRE-GROUT | DWITT | Approved | IVRS - Inspection 0000* |
09/21/2001 | EXCAVATION/LAYOUT REBAR & ZON | DWITT | Approved | IVRS - Inspection 0000* |
11/14/2001 | MECHANICAL - FINAL | JMILITEL | Approved | PARTIAL FIRE SMOKE DAMPER MISSING ON EXHAUST FROM BATTERY ROOM. CHECK W/ENGINEER FOR DIRECTION. |
11/14/2001 | PLUMBING - FINAL | FMCCLURE | Approved | IVRS - Inspection 0000*NO PLANS ON JOB. |
11/14/2001 | ELECTRIC - FINAL | MCAPISTR | Approved | IVRS - Inspection 0000* |
11/14/2001 | ELECTRIC - ABOVE CEILING | MCAPISTR | Approved | IVRS - Inspection 0000* |
01/30/2002 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | |
01/30/2002 | PERMIT FINALED | DWITT | Approved | |
01/30/2002 | SIGN - FINAL | JYBARRA | Approved | IVRS - Inspection 0000* |
01/30/2002 | OUTDOOR LIGHTING FINAL | MCAPISTR | Approved | IVRS - Inspection 0000*1.) WALL PACS OK. |
01/30/2002 | BUILDING - FINAL | DWITT | Approved | IVRS - Inspection 0000* |
02/05/2002 | PLUMBING - INTERMEDIATE | FMCCLURE | Approved |