Permit Details

Status:
C of o
Type:
COMMERCIAL ALTERATION
Address:
6501 E BENSON HY
Apply Date:
03/12/2001
Applicant:
SONORA EXPEDITING
Description:
TI:OFFICE
Contractors:
  • RALLY CONSTRUCTION COMPANY INC ,

Permit Reviews

Permit Number - T01CM01188
Permit Status: C of o
Permit Description: TI:OFFICE
Start Date Submittal Complete Date Status  
03/12/2001 COMMERCIAL TI 04/17/2001 COMPLETED Review Details
04/17/2001 RESUBMITTAL 05/04/2001 COMPLETED Review Details
04/17/2001 SITE 05/04/2001 COMPLETED Review Details
05/04/2001 OTHER 05/04/2001 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T01CM01188
Permit Status: C of o
Permit Description: TI:OFFICE
Total Outstanding Activity Conditions - 1
Date Name
03/12/2001 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T01CM01188
Permit Description: TI:OFFICE
Total Completed Inspections - 21
Date Description Inspector Results Comments
05/15/2001 SHEET ROCK NAILING DWITT Approved IVRS - Inspection 0000*SHT. ROCK
05/22/2001 PLUMBING - ROUGH, SOIL FMCCLURE Approved IVRS - Inspection 0000*
06/26/2001 ELECTRIC - INTERMEDIATE RMAJUTA Approved IVRS - Inspection 0000*ELECT RM 4-3" EMTS ABOVE CEILING & WALLS & CEILING OK TO COVER HALL ENTRY CEILING OK TO COVER
06/28/2001 MECHANICAL - ABOVE CEILING JMILITEL Approved IVRS - Inspection 0000*PROVIDE AN ACCESS DOOR TO FIRE DAMPER ON HALLWAY WALL.
06/28/2001 ELECTRIC - UNDERGROUND RMAJUTA Approved IVRS - Inspection 0000*1.) 4" PVC'S TEP POLE TO TRANS 4 3" PVC'S TRANS TO BLDG 2 2" PVC'S BLDG TO GEN 3.) 1 1/4 PVC BLDG TO GEN 4.) 3/4 PVC' BLDG TO GEN 2 GROUND RODS W/3/0 CU. ALL OK TO COVER
06/29/2001 FRAMING DWITT Approved IVRS - Inspection 0000*BATTERY WALLS STOP @ CEIL. PLEASE HAVE ARCHITECT REVIEW THE NOTE RE: RAISING THE WALL TO DECK OK LID.
07/16/2001 BOILER FINAL RLOHRMAN Approved IVRS - Inspection 0000*
07/16/2001 BOILER - EXPANSION TANK RLOHRMAN Approved IVRS - Inspection 0000*
07/16/2001 BOILER UNFIRED PRESSURE VESSEL RLOHRMAN Approved IVRS - Inspection 0000*HANSON 2001 NB178545 WP125PSI S#401496
09/21/2001 REINFORCED MASONRY PRE-GROUT DWITT Approved IVRS - Inspection 0000*
09/21/2001 EXCAVATION/LAYOUT REBAR & ZON DWITT Approved IVRS - Inspection 0000*
11/14/2001 MECHANICAL - FINAL JMILITEL Approved PARTIAL FIRE SMOKE DAMPER MISSING ON EXHAUST FROM BATTERY ROOM. CHECK W/ENGINEER FOR DIRECTION.
11/14/2001 PLUMBING - FINAL FMCCLURE Approved IVRS - Inspection 0000*NO PLANS ON JOB.
11/14/2001 ELECTRIC - FINAL MCAPISTR Approved IVRS - Inspection 0000*
11/14/2001 ELECTRIC - ABOVE CEILING MCAPISTR Approved IVRS - Inspection 0000*
01/30/2002 MECHANICAL - INTERMEDIATE JMILITEL Approved
01/30/2002 PERMIT FINALED DWITT Approved
01/30/2002 SIGN - FINAL JYBARRA Approved IVRS - Inspection 0000*
01/30/2002 OUTDOOR LIGHTING FINAL MCAPISTR Approved IVRS - Inspection 0000*1.) WALL PACS OK.
01/30/2002 BUILDING - FINAL DWITT Approved IVRS - Inspection 0000*
02/05/2002 PLUMBING - INTERMEDIATE FMCCLURE Approved