Permit Number: T01CM01188
Parcel: 141090190

Address:
6501 E BENSON HY

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T01CM01188
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/12/2001 JIM EGAN FIRE REVIEW Approved 1. BATTERY SYSTEMS SHALL COMPLY WITH 1997 UNIFORM FIRE CODE ARTICLE 64.
2. SEPARATE PERMIT REQUIRED FOR INSTALLATION OF ABOVEGROUND FUEL STORAGE TANKS.
03/26/2001 RANDY SCHULER ELECTRICAL-COMMERCIAL REVIEW Denied E1
1) Keynote 3 indicates a relocation and connection to an existing well disconnect which is referenced on E2 by keynote 3. Please clarify the location of the equipment on E2.
E2
1) Identify all the equipment connected to panel DP by utilizing an alpha designation that corresponds with page E3 feeder legend.
2) Provide a motor rated switch with appropriately sized overloads for FSD. In addition add a 15 amp circuit breaker in the panel. See page E4 circuit CO-B-37.
3) Clarify the intent of the term "Switch Lites". See keynote 24, typical of 7 circuits.
4) Keynote 11 references an air dryer however the keynote on the plan points to TU-1.
5) There are 2 keynotes 30 in the keynote legend.
E3
1) The fuse protecting the primary of T1 is too small.
2) SP1 and SP2 are shown as 2HP however on M2 they are specified as 5HP.
3) Remove the bonding jumper from the neutral to ground in panel RP. Provide a ground wire in the feeder. As shown the neutral and the conduit are in parallel and will each carry a portion of the current.
E4
1) Reduce circuit CO-B-5 to 15 amps.
2) It appears circuits CO-B-7, 9,11,21,29,31,33,35 are existing. Please clarify.
3) Please provide the Z of T1.
03/30/2001 JKOZUCH FLOODPLAIN REVIEW Needs Review
03/30/2001 DAVID RIVERA ZONING REVIEW Denied
03/30/2001 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied
04/03/2001 HOLLY PEARCE PLUMBING-COMMERCIAL REVIEW Passed
04/03/2001 HOLLY PEARCE MECHANICAL-COMMERCIAL REVIEW Denied
04/17/2001 JKOZUCH WWM REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
04/17/2001 JKOZUCH OUT TO CUSTOMER Completed
04/17/2001 JKOZUCH REJECT SHELF Completed
04/17/2001 JKOZUCH APPROVAL SHELF Completed
04/17/2001 JKOZUCH REJECT SHELF Completed