Permit: T00ME01495
Permit Details
Status:
Expired
Type:
MULTI FAMILY OTHER
Address:
2861 N COLUMBUS BL #16
Address NEW:
2861 N COLUMBUS BL #16
Apply Date:
12/20/2000
Applicant:
COLUMBUS PARK LLC
Description:
INSTALL:AC
Permit Reviews
Permit Number - T00ME01495
Permit Status: Expired
Permit Description: INSTALL:AC
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 12/20/2000 | MECHANICAL | 12/20/2000 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T00ME01495
Permit Status: Expired
Permit Description: INSTALL:AC
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 12/20/2000 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T00ME01495
Permite Description: INSTALL:AC
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/27/2000 | MECHANICAL - FINAL | N/A | Denied | IVRS - Inspection 0999* INSTALL CONDENSATE DRAIN TO AN APPROVED LOCATIONS CANNOT HAVE CONTROL WIRING EXPOSED, USE CONDUIT OR OTHER MEANS MARK DATA PLATE W/PROPER HEAT STRIP INSTALLED AND FUSE UNIT ACCORDINGLY CANNOT USE #8 WIRE ON A 60 AMP CIRCUIT |