Permit: T00ME01495

Parcel: 11006159B

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
12/27/2000 MECHANICAL - FINAL Denied IVRS - Inspection 0999*
INSTALL CONDENSATE DRAIN TO AN APPROVED LOCATIONS
CANNOT HAVE CONTROL WIRING EXPOSED, USE CONDUIT OR OTHER MEANS
MARK DATA PLATE W/PROPER HEAT STRIP INSTALLED AND FUSE UNIT ACCORDINGLY
CANNOT USE #8 WIRE ON A 60 AMP CIRCUIT