Permit: T00ME01309
Permit Details
Status:
Final
Type:
SINGLE FAMILY OTHER
Address:
8261 E APPOMATTOX ST
Address NEW:
8261 E APPOMATTOX ST
Apply Date:
11/13/2000
Applicant:
RITE WAY VENTILATING CO , *C
Description:
HEATING & COOLING UNIT:INSTALL
Outstanding Activity Conditions
Permit Number - T00ME01309
Permit Status: Final
Permit Description: HEATING & COOLING UNIT:INSTALL
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 11/13/2000 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T00ME01309
Permit Description: HEATING & COOLING UNIT:INSTALL
Total Completed Inspections - 1
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/20/2000 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection 0999* 60 AMP FUSES TOO LARGE FOR #8 WIRE USE A FITTING WHERE WIRES PENETRATE A/C CABINET USE AN APPROVED FITTING ON CONDENSATE DRAIN TERMINATING INTO A WASTE VENT CORRECT AND RECALL FOR FINAL |