Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/03/2001 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* ALL CORRECTIONS HAVE BEEN MADE |
|
| 11/20/2000 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* 60 AMP FUSES TOO LARGE FOR #8 WIRE USE A FITTING WHERE WIRES PENETRATE A/C CABINET USE AN APPROVED FITTING ON CONDENSATE DRAIN TERMINATING INTO A WASTE VENT CORRECT AND RECALL FOR FINAL |