Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address NEW:
2140 W WINDOW ROCK DR
Apply Date:
11/09/2000
Applicant:
G T R HEATING AND AIR CONDITIONI
Description:
HEATING & COOLING UNIT:REPLACE

Outstanding Activity Conditions

Permit Number - T00ME01301
Permit Status: Expired
Permit Description: HEATING & COOLING UNIT:REPLACE
Total Outstanding Activity Conditions - 1
Date Name
11/09/2000 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T00ME01301
Permite Description: HEATING & COOLING UNIT:REPLACE
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
12/06/2000 MECHANICAL - FINAL N/A Denied IVRS - Inspection 0999*
60 AMP FUSES ARE TOO LARGE FOR #8 WIRE USE #6
SEAL AROUND SUPPLY AND RETURN CONNECTIONS TO UNIT BETTER
CORRECT AND RECALL FOR FINAL

Documents

File Name Document Type  
None DOCUMENTS VIEW