Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/06/2000 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* 60 AMP FUSES ARE TOO LARGE FOR #8 WIRE USE #6 SEAL AROUND SUPPLY AND RETURN CONNECTIONS TO UNIT BETTER CORRECT AND RECALL FOR FINAL |