Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Apply Date:
11/03/2000
Applicant:
KELLY AIR CONDITIONING ,
Description:
INSTALL HEATING & COOLING UNIT
Contractors:
  • KELLY AIR CONDITIONING , *C

Outstanding Activity Conditions

Permit Number - T00ME01271
Permit Status: Expired
Permit Description: INSTALL HEATING & COOLING UNIT
Total Outstanding Activity Conditions - 1
Date Name
11/03/2000 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T00ME01271
Permite Description: INSTALL HEATING & COOLING UNIT
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
11/06/2000 MECHANICAL - FINAL N/A Denied IVRS - Inspection 0999*
#8 WIRE NOT ACCEPTABLE FOR 60 AMP CIRCUIT
STRAP FLEX DUCT 4" ABOVE GROUND AND MIN 1 1/2" WIDE STRAP EVERY 4'
PAINT EXPOSED PVC W/LATEX PAINT
PROTECT FLEX DUCT FROM RAIN

Documents

File Name Document Type  
None DOCUMENTS VIEW