Permit: T00ME01271

Parcel: 140371390

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
11/06/2000 MECHANICAL - FINAL Denied IVRS - Inspection 0999*
#8 WIRE NOT ACCEPTABLE FOR 60 AMP CIRCUIT
STRAP FLEX DUCT 4" ABOVE GROUND AND MIN 1 1/2" WIDE STRAP EVERY 4'
PAINT EXPOSED PVC W/LATEX PAINT
PROTECT FLEX DUCT FROM RAIN