Last Inspection Date Description Inspector Results Comments
10/02/2000 MECHANICAL - FINAL N/A Denied IVRS - Inspection 0999*
1. PAINT EXPOSED PVC W/LATEX PAINT
FLEX DUCT MUST BE MIN 4" ABOVE EARTH AS PER SEC 603.2.2 1994 UMC
STRAP FLEX DUCT MIN 4' APART SEC 6.509.1 APPR
INSTALL A RAIN SHEILD BETWEEN A/C UNIT AND WALL
USE AN APPROVED BASE FOR A/C EQUIPMENT MIN 3" ABOVE GRADE SEC 1105.2.1