Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/02/2000 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* 1. PAINT EXPOSED PVC W/LATEX PAINT FLEX DUCT MUST BE MIN 4" ABOVE EARTH AS PER SEC 603.2.2 1994 UMC STRAP FLEX DUCT MIN 4' APART SEC 6.509.1 APPR INSTALL A RAIN SHEILD BETWEEN A/C UNIT AND WALL USE AN APPROVED BASE FOR A/C EQUIPMENT MIN 3" ABOVE GRADE SEC 1105.2.1 |
|
| 09/29/2000 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* A/C FINAL DUCTING TO BE SUSPENDED 6" OFF GROUND (OR AS CLOSE TO 6" AS HOME CLEARANCE 2.# 8 WIRE NOT RATED FOR 60 AMP BREAKER IN SERVICE PANEL 3. CONDENSATE DRAIN LINE PLUGGED WITH SAND 4. CONDENSATE DRAIN LINE NOT PAINTED 5. NO GAS PRESSURE TEST |