Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Address NEW:
4648 E SPEEDWAY BL
Apply Date:
05/16/2000
Applicant:
TEMP CON INC ,
Description:
GAS PACK
Contractors:
  • TEMP CON INC ,

Completed Inspections

Permit Status: Final
Permit Number: T00ME00532
Permit Description: GAS PACK
Total Completed Inspections - 1
Date Description Inspector Results Comments
06/07/2000 MECHANICAL - FINAL CWILLIAM Approved ADDTL COMMS - NOTE TO OCCUPANT/OWNER THIS IS A 5 TON PHY. UNIT SHOULD HAVE A 60 AMP CIRCUIT TO ASSURE GOOD OPERATION. HOWEVER MINIMUM CIRCUIT AMPACTIY IS 44.0 AMP CIRCUIT AS LISTED BY MANUFACTURE. CONTRACTOR FUSED AT 50 AMPS, OK FOR #8 WIRE FUSE AT THE PREFERABLE 60 AMPS COULD REQUIRE #6. HAVE TO ACCEPT AS RUN.