Permit: T00ME00532
Permit Details
Apply Date:
05/16/2000
Applicant:
TEMP CON INC ,
Description:
GAS PACK
Contractors:
- TEMP CON INC ,
Completed Inspections
Permit Status: Final
Permit Number: T00ME00532
Permit Description: GAS PACK
Total Completed Inspections - 1
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/07/2000 | MECHANICAL - FINAL | CWILLIAM | Approved | ADDTL COMMS - NOTE TO OCCUPANT/OWNER THIS IS A 5 TON PHY. UNIT SHOULD HAVE A 60 AMP CIRCUIT TO ASSURE GOOD OPERATION. HOWEVER MINIMUM CIRCUIT AMPACTIY IS 44.0 AMP CIRCUIT AS LISTED BY MANUFACTURE. CONTRACTOR FUSED AT 50 AMPS, OK FOR #8 WIRE FUSE AT THE PREFERABLE 60 AMPS COULD REQUIRE #6. HAVE TO ACCEPT AS RUN. |