Inspection History Details
Inspection Status: Correction Required
Inspection History: MECHANICAL - FINAL
Permit Number - T00ME00532
Inspection Description - MECHANICAL - FINAL
Inspection Status - Correction Required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/07/2000 | MECHANICAL - FINAL | Correction Required | ADDTL COMMS - NOTE TO OCCUPANT/OWNER THIS IS A 5 TON PHY. UNIT SHOULD HAVE A 60 AMP CIRCUIT TO ASSURE GOOD OPERATION. HOWEVER MINIMUM CIRCUIT AMPACTIY IS 44.0 AMP CIRCUIT AS LISTED BY MANUFACTURE. CONTRACTOR FUSED AT 50 AMPS, OK FOR #8 WIRE FUSE AT THE PREFERABLE 60 AMPS COULD REQUIRE #6. HAVE TO ACCEPT AS RUN. | |
| 05/17/2000 | MECHANICAL - FINAL | Correction Required | ADDTL COMMS - 1. NUMBER 8 WIRE NOT ACCEPTABLE FOR 60 AMPS USE NUMBER 6 2. BLOCK CONDENSATE CHAIN EVERY 4 3. TERMINATE CONDENSATE INTO AN APPROVED FITTING CORRECT AND RECALL FOR FIANL | |
| 05/17/2000 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* |