Permit: T00ME00530
Permit Details
Apply Date:
05/15/2000
Applicant:
KELLY AIR CONDITIONING ,
Description:
AIR COND
Contractors:
- KELLY AIR CONDITIONING ,
Outstanding Inspections
Permit Status: Expired
Permit Number: T00ME00530
Permite Description: AIR COND
Total Outstanding Inspections - 1
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/16/2000 | MECHANICAL - FINAL | N/A | Correction Required | ADDTL COMMS - 1. NEED TO SEE LISTING FROM AND APPROVED TESTING AGENCY ( A.L., ASTM, ETC) FOR PLASTIC CONDENSOR PAD. UMC 1994 SEC 1105.2.1 EVEN IF THIS PAD IS LISTED, IT STILL DOES NOT MEET THE MIN. 3 ABOVE GRADE. 2. ANCHOR EQUIPMENT AS PER SEC. 304.4 |