Inspection Status: Correction Required
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/16/2000 |
MECHANICAL - FINAL |
|
Correction Required |
ADDTL COMMS - 1. NEED TO SEE LISTING FROM AND APPROVED TESTING AGENCY ( A.L., ASTM, ETC) FOR PLASTIC CONDENSOR PAD. UMC 1994 SEC 1105.2.1 EVEN IF THIS PAD IS LISTED, IT STILL DOES NOT MEET THE MIN. 3 ABOVE GRADE. 2. ANCHOR EQUIPMENT AS PER SEC. 304.4 |
| 05/16/2000 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* |