Permit: T00ME00530

Parcel: 140321930

Inspection Status: Correction Required

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
05/16/2000 MECHANICAL - FINAL Correction Required ADDTL COMMS - 1. NEED TO SEE LISTING FROM AND APPROVED TESTING AGENCY ( A.L., ASTM, ETC) FOR PLASTIC CONDENSOR PAD. UMC 1994 SEC 1105.2.1 EVEN IF THIS PAD IS LISTED, IT STILL DOES NOT MEET THE MIN. 3 ABOVE GRADE. 2. ANCHOR EQUIPMENT AS PER SEC. 304.4
05/16/2000 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*