Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address NEW:
9410 E LURLENE DR
Apply Date:
05/11/2000
Applicant:
ANDROS REFRIGERATION INC ,
Description:
AIR COND:FURNACE
Contractors:
  • ANDROS REFRIGERATION INC ,

Outstanding Inspections

Permit Status: Expired
Permit Number: T00ME00501
Permite Description: AIR COND:FURNACE
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
09/06/2000 MECHANICAL - FINAL N/A Partial Approval IVRS - Inspection 0000*
REMOVE GAS VALVE IN WATER HEATER CLOSET AND CAP OFF
CAP OFF UNUSED PORTION OF OLD FURNACE VENT
PAINT EXPOSED PVC W/LATEX PAINT. SPRAY PAINT WILL NOT BE ACCEPTED
WHEN TERMINATING CONDENSATE DRAIN INTO A WASTE VENT THE MIN SIZE VENT SHALL BE 2" IF YOU TERMINATE INTO THE SIDE OF A VENT USE AN APPROVED FITTING
CORRECT AND RECALL FOR FINAL