Inspection History Details
Inspection Status: Partial Approval
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/06/2000 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* REMOVE GAS VALVE IN WATER HEATER CLOSET AND CAP OFF CAP OFF UNUSED PORTION OF OLD FURNACE VENT PAINT EXPOSED PVC W/LATEX PAINT. SPRAY PAINT WILL NOT BE ACCEPTED WHEN TERMINATING CONDENSATE DRAIN INTO A WASTE VENT THE MIN SIZE VENT SHALL BE 2" IF YOU TERMINATE INTO THE SIDE OF A VENT USE AN APPROVED FITTING CORRECT AND RECALL FOR FINAL |