Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
3233 E 28TH ST
Address NEW:
3233 E 28TH ST
Apply Date:
12/20/2000
Applicant:
DAVID HALL
Description:
ELECTRIC:RECONNECT:SFR

Outstanding Activity Conditions

Permit Number - T00EL02912
Permit Status: Expired
Permit Description: ELECTRIC:RECONNECT:SFR
Total Outstanding Activity Conditions - 1
Date Name
12/20/2000 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T00EL02912
Permite Description: ELECTRIC:RECONNECT:SFR
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
12/28/2000 ELECTRIC - RECONNECT N/A Denied IVRS - Inspection 0210*
NO ACCESS
THE MAIN ELECTRIC LOAD CENTER IS OF THE SPLIT BUSS TYPE AND ADDED CIRCUITS HAVE CREATED A VIOLATION OF THE SIX MAIN DISCONNECTS RULE OF NEC ART 230.
THE ADDED CIRCUITS MAY HAVE ALSO CAUSED AN POSSIBLE OVERLOAD TO THE ELECTRICAL SERVICE
THE STOVE/ RANGE RECEPTACLE MUST BE FIRMLY ATTACHED TO THE WALL STRUCTURE
THE WIRING OF THE BATHROOM LIGHT FIXTURES MUST BE TERMINATED IN AN APPROVED EXTENSION BOX
RECEPTACLES IN BATHROOMS SHOULD BE OF THE GFI TYPE FOR PERSONNEL PROTECTION