Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/28/2000 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection 0210* NO ACCESS THE MAIN ELECTRIC LOAD CENTER IS OF THE SPLIT BUSS TYPE AND ADDED CIRCUITS HAVE CREATED A VIOLATION OF THE SIX MAIN DISCONNECTS RULE OF NEC ART 230. THE ADDED CIRCUITS MAY HAVE ALSO CAUSED AN POSSIBLE OVERLOAD TO THE ELECTRICAL SERVICE THE STOVE/ RANGE RECEPTACLE MUST BE FIRMLY ATTACHED TO THE WALL STRUCTURE THE WIRING OF THE BATHROOM LIGHT FIXTURES MUST BE TERMINATED IN AN APPROVED EXTENSION BOX RECEPTACLES IN BATHROOMS SHOULD BE OF THE GFI TYPE FOR PERSONNEL PROTECTION |
|
| 12/22/2000 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection 0920* |