Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T00EL02911
Permit Details
Apply Date:
12/20/2000
Applicant:
MW MCLAUGHLIN
Description:
INSTALL:ELECTRIC PEDESTAL
Permit Reviews
Permit Number - T00EL02911
Permit Status: Expired
Permit Description: INSTALL:ELECTRIC PEDESTAL
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
12/20/2000 | ELECTRICAL | 12/20/2000 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T00EL02911
Permit Status: Expired
Permit Description: INSTALL:ELECTRIC PEDESTAL
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
12/20/2000 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T00EL02911
Permite Description: INSTALL:ELECTRIC PEDESTAL
Total Outstanding Inspections - 3
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
ELECTRIC - TEMPORARY SERVICE | N/A | Not Inspected | ||
ELECTRIC - FINAL | N/A | Not Inspected | ||
12/21/2000 | ELECTRIC - CABLE DROP | N/A | Denied | IVRS - Inspection 0999* ACORN CLAMPS INCORRECTLY INSTALLED GROUNDS CLAMPS INCORRECTLY INSTALLED GROUND RODS NOT 6' OR MORE APART I DON'T UNDERSTAND WHY 2ND GROUND ROD IS UPSIDE DOWN. INSTALL NEW GROUND ROD OR UNCOVER OLD ONE SO I CAN SEE THAT IT IS 8' LONG |