Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/21/2000 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0999* ACORN CLAMPS INCORRECTLY INSTALLED GROUNDS CLAMPS INCORRECTLY INSTALLED GROUND RODS NOT 6' OR MORE APART I DON'T UNDERSTAND WHY 2ND GROUND ROD IS UPSIDE DOWN. INSTALL NEW GROUND ROD OR UNCOVER OLD ONE SO I CAN SEE THAT IT IS 8' LONG |