Permit: T00EL02911

Parcel: 11928143A


Addresses:

2426 W 44TH ST #02


Inspection Status: Denied

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T00EL02911

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Denied

Date Description Inspector Results Comments
12/21/2000 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0999*
ACORN CLAMPS INCORRECTLY INSTALLED
GROUNDS CLAMPS INCORRECTLY INSTALLED
GROUND RODS NOT 6' OR MORE APART
I DON'T UNDERSTAND WHY 2ND GROUND ROD
IS UPSIDE DOWN. INSTALL NEW GROUND ROD OR UNCOVER OLD ONE SO I CAN SEE THAT IT IS 8' LONG