Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T00EL02729
Permit Details
Apply Date:
11/24/2000
Applicant:
AC ARTISANS ELECTRICAL CONTRACT
Description:
ELECTRIC SERVICE:UPGRADE 30 TO 100 AMP
Outstanding Activity Conditions
Permit Number - T00EL02729
Permit Status: Final
Permit Description: ELECTRIC SERVICE:UPGRADE 30 TO 100 AMP
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
11/24/2000 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T00EL02729
Permit Description: ELECTRIC SERVICE:UPGRADE 30 TO 100 AMP
Total Completed Inspections - 2
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/20/2000 | ELECTRIC - FINAL | RMAJUTA | Approved | THE SERVICE IS NOT GROUNDED, #1 IS GROUNDED #2 NOT NEED TO CONNECT GROUND SYSTEM TO SERVICE #2 SEAL ALL HOLES AT APT PANEL OUTSIDE (BOTTOM) SUPPORT CARFLEX BELOW PANEL J-BOX ABOVE PANEL OUTSIDE REQUIRED TO BE SUPPORTED ITSELF, CANNOT BE SUPPORTED BY EMT FEEDING IT SUPPORT CARFLEX ON ROOF SUPPORT J BOX BY DOOR UNIT TO BE OPEN FOR INSPECTION FOR FINAL LABEL PANEL CIRCUITS WHERE IS WATER BOND AND GAS BOND 2ND STRUCTURE IF NO GAS CONNECTION PLEASE INDICATE |
01/24/2001 | PERMIT FINALED | DSANTACR | Approved |