Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/24/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* OK TO CLEAR SP #2 |
|
| 12/20/2000 | ELECTRIC - FINAL | Denied | THE SERVICE IS NOT GROUNDED, #1 IS GROUNDED #2 NOT NEED TO CONNECT GROUND SYSTEM TO SERVICE #2 SEAL ALL HOLES AT APT PANEL OUTSIDE (BOTTOM) SUPPORT CARFLEX BELOW PANEL J-BOX ABOVE PANEL OUTSIDE REQUIRED TO BE SUPPORTED ITSELF, CANNOT BE SUPPORTED BY EMT FEEDING IT SUPPORT CARFLEX ON ROOF SUPPORT J BOX BY DOOR UNIT TO BE OPEN FOR INSPECTION FOR FINAL LABEL PANEL CIRCUITS WHERE IS WATER BOND AND GAS BOND 2ND STRUCTURE IF NO GAS CONNECTION PLEASE INDICATE |