Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Apply Date:
11/14/2000
Applicant:
D AND D SIGNS ,
Description:
SIGN:ELECTRIC:1592
Contractors:
  • D AND D SIGNS ,

Outstanding Activity Conditions

Permit Number - T00EL02666
Permit Status: Final
Permit Description: SIGN:ELECTRIC:1592
Total Outstanding Activity Conditions - 1
Date Name
11/14/2000 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T00EL02666
Permit Description: SIGN:ELECTRIC:1592
Total Completed Inspections - 4
Date Description Inspector Results Comments
11/24/2000 SIGN ELECTRIC RMAJUTA Approved IVRS - Inspection 0999$
SIGN DISCONNECT BOX TO BE IDENTIFIED AND SUPPORTED
FLEX FROM SWITCH TO TRANSFORMER TO BE SUPPORTED NOT ON CEILING
GROUND WIRE IN TRANSFORMER BOX NOT CONNECTED TO ENCLOSURE
TRANSFORMER TO BE SECURED TO BOX
FLEX USED TO HOUSE GTO SHALL BE GROUNDED
METAL FRAMES OF LETTERS AND SYMBOL SHALL BE GROUNDED
IMPROPER TRANSITION FROM END OF FLEX O NEON TUBING THUR WALL MUST USE A PROPER AND LISTED FITTING
THERE IS NO SUPPORT OF FLEX HOUSING GTO
AT SWITCH RUN FLEX ALL THE WAY INTO FITTING
NO CITY STICKER PUT ON SIGN NO CURRENT OR AMP RATING
02/07/2001 SIGN SHOP LHANLY Approved IVRS - Inspection 0000*
03/07/2001 PERMIT FINALED JSONKIN Approved
03/07/2001 SIGN INSPECTION JSONKIN Approved IVRS - Inspection 0000*