Permit: T00EL02666

Parcel: 12701005D

Inspection Status: Approved

Inspection History: SIGN ELECTRIC

Permit Number - T00EL02666

Inspection Description - SIGN ELECTRIC

Inspection Status - Approved

Date Description Inspector Results Comments
02/07/2001 SIGN ELECTRIC Approved IVRS - Inspection 0000*
11/24/2000 SIGN ELECTRIC Denied IVRS - Inspection 0999$
SIGN DISCONNECT BOX TO BE IDENTIFIED AND SUPPORTED
FLEX FROM SWITCH TO TRANSFORMER TO BE SUPPORTED NOT ON CEILING
GROUND WIRE IN TRANSFORMER BOX NOT CONNECTED TO ENCLOSURE
TRANSFORMER TO BE SECURED TO BOX
FLEX USED TO HOUSE GTO SHALL BE GROUNDED
METAL FRAMES OF LETTERS AND SYMBOL SHALL BE GROUNDED
IMPROPER TRANSITION FROM END OF FLEX O NEON TUBING THUR WALL MUST USE A PROPER AND LISTED FITTING
THERE IS NO SUPPORT OF FLEX HOUSING GTO
AT SWITCH RUN FLEX ALL THE WAY INTO FITTING
NO CITY STICKER PUT ON SIGN NO CURRENT OR AMP RATING
11/21/2000 SIGN ELECTRIC Not ready for Inspection IVRS - Inspection 0000*
IF USING A TRANSFORMER WITH SECONDARY OUT PUT OF 7, 500 VOLTA (OVER) 1999 NEC SECTION #600 REQUIRES IT TO BE A GROUND FAULT PROTECTED TYPE
WILL NEED TO SEE DISCONNECT