Inspection History Details
Inspection Status: Approved
Inspection History: SIGN ELECTRIC
Permit Number - T00EL02666
Inspection Description - SIGN ELECTRIC
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/07/2001 | SIGN ELECTRIC | Approved | IVRS - Inspection 0000* | |
11/24/2000 | SIGN ELECTRIC | Denied | IVRS - Inspection 0999$ SIGN DISCONNECT BOX TO BE IDENTIFIED AND SUPPORTED FLEX FROM SWITCH TO TRANSFORMER TO BE SUPPORTED NOT ON CEILING GROUND WIRE IN TRANSFORMER BOX NOT CONNECTED TO ENCLOSURE TRANSFORMER TO BE SECURED TO BOX FLEX USED TO HOUSE GTO SHALL BE GROUNDED METAL FRAMES OF LETTERS AND SYMBOL SHALL BE GROUNDED IMPROPER TRANSITION FROM END OF FLEX O NEON TUBING THUR WALL MUST USE A PROPER AND LISTED FITTING THERE IS NO SUPPORT OF FLEX HOUSING GTO AT SWITCH RUN FLEX ALL THE WAY INTO FITTING NO CITY STICKER PUT ON SIGN NO CURRENT OR AMP RATING |
|
11/21/2000 | SIGN ELECTRIC | Not ready for Inspection | IVRS - Inspection 0000* IF USING A TRANSFORMER WITH SECONDARY OUT PUT OF 7, 500 VOLTA (OVER) 1999 NEC SECTION #600 REQUIRES IT TO BE A GROUND FAULT PROTECTED TYPE WILL NEED TO SEE DISCONNECT |