Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T00EL02377
Permit Details
Apply Date:
10/06/2000
Applicant:
PUEBLO ELECTRIC SERVICES ''T''
Description:
UPGRADE:ELECTRIC:60 TO 100 AMP
Contractors:
- PUEBLO ELECTRIC SERVICES ''T''
Outstanding Activity Conditions
Permit Number - T00EL02377
Permit Status: Expired
Permit Description: UPGRADE:ELECTRIC:60 TO 100 AMP
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
10/06/2000 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T00EL02377
Permite Description: UPGRADE:ELECTRIC:60 TO 100 AMP
Total Outstanding Inspections - 1
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/09/2000 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection 0999* NEED SCREWS FOR LABEL LABEL BRANCH BREAKERS 2ND AND 3RD RISER SUPPORTS NOT ATTACHED TO WALL USE AT LEAST 1/4" SUPPORTS SECURE BOX AND SEAL TITE SUPPORT CONDUITS WITH IN 3' OF BOXES RISER CLEARENCES TO BE 8' ABOVE ROOF 230-24 (A) OTHER BUILDING ROOF LIGHT DOES NOT MEET LIGHTING ORDINACE # 8210 SEC 5 |