Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/09/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* NEED SCREWS FOR LABEL LABEL BRANCH BREAKERS 2ND AND 3RD RISER SUPPORTS NOT ATTACHED TO WALL USE AT LEAST 1/4" SUPPORTS SECURE BOX AND SEAL TITE SUPPORT CONDUITS WITH IN 3' OF BOXES RISER CLEARENCES TO BE 8' ABOVE ROOF 230-24 (A) OTHER BUILDING ROOF LIGHT DOES NOT MEET LIGHTING ORDINACE # 8210 SEC 5 |