Permit: T00EL02219
Permit Details
Apply Date:
09/18/2000
Applicant:
DAVIS ENTERPRISES
Description:
RECONNECT:ELECTRIC:CARNIVAL
Outstanding Activity Conditions
Permit Number - T00EL02219
Permit Status: Expired
Permit Description: RECONNECT:ELECTRIC:CARNIVAL
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
09/18/2000 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T00EL02219
Permite Description: RECONNECT:ELECTRIC:CARNIVAL
Total Outstanding Inspections - 1
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/29/2000 | ELECTRIC - FINAL | N/A | Partial Approval | INSTALL BREAKER BLANKS AT UNUSED BREAKER SPACES NEXT TO SUPER SLIDE PROVIDE INDIVIUAL OVERCURRENT PROTECTIONJ FOR EACH RIDE (DO NOT JUST TAP OFF THE BUS BAR UNLESS WIRE IS RATED FOR THE SIZE OF THE DISTRIBUTION FEEDER) SCRAPE PAINT OFF WHERE ALL DISCONNECTS |