Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T00EL02219


Addresses:

7149 E 22ND ST

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/29/2000 ELECTRIC - FINAL Partial Approval INSTALL BREAKER BLANKS AT UNUSED
BREAKER SPACES NEXT TO SUPER SLIDE
PROVIDE INDIVIUAL OVERCURRENT PROTECTIONJ FOR EACH RIDE (DO NOT JUST TAP OFF THE BUS BAR UNLESS WIRE IS RATED FOR THE SIZE OF THE DISTRIBUTION FEEDER) SCRAPE PAINT OFF WHERE ALL DISCONNECTS