Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address NEW:
2933 E FLORENCE DR
Apply Date:
08/16/2000
Applicant:
CADILLAC ELECTRIC ,
Description:
200AMP:UPGRADE
Contractors:
  • CADILLAC ELECTRIC ,

Outstanding Activity Conditions

Permit Number - T00EL01999
Permit Status: Expired
Permit Description: 200AMP:UPGRADE
Total Outstanding Activity Conditions - 1
Date Name
08/16/2000 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T00EL01999
Permite Description: 200AMP:UPGRADE
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
08/18/2000 ELECTRIC - FINAL N/A Denied IVRS - Inspection 0245*
#6 WIRE ON OVERSIZED BREAKER SHOULD BE ON 60 AMP
BOND BUSHING REQUIRED ON 2" CONDUIT BOTH ENDS NEC 250-94
2" EMT CONNECTOR MUST BE SEATED FLUSH ON PANEL APPEARS TO BE TILTED