Permit: T00EL01999
Permit Details
Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
2933 E FLORENCE DR
Address NEW:
2933 E FLORENCE DR
Apply Date:
08/16/2000
Applicant:
CADILLAC ELECTRIC ,
Description:
200AMP:UPGRADE
Contractors:
- CADILLAC ELECTRIC ,
Outstanding Activity Conditions
Permit Number - T00EL01999
Permit Status: Expired
Permit Description: 200AMP:UPGRADE
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 08/16/2000 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T00EL01999
Permite Description: 200AMP:UPGRADE
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/18/2000 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection 0245* #6 WIRE ON OVERSIZED BREAKER SHOULD BE ON 60 AMP BOND BUSHING REQUIRED ON 2" CONDUIT BOTH ENDS NEC 250-94 2" EMT CONNECTOR MUST BE SEATED FLUSH ON PANEL APPEARS TO BE TILTED |