Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/18/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* #6 WIRE ON OVERSIZED BREAKER SHOULD BE ON 60 AMP BOND BUSHING REQUIRED ON 2" CONDUIT BOTH ENDS NEC 250-94 2" EMT CONNECTOR MUST BE SEATED FLUSH ON PANEL APPEARS TO BE TILTED |