Permit: T00EL01999

Parcel: 112042970


Addresses:

2933 E FLORENCE DR

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/18/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0245*
#6 WIRE ON OVERSIZED BREAKER SHOULD BE ON 60 AMP
BOND BUSHING REQUIRED ON 2" CONDUIT BOTH ENDS NEC 250-94
2" EMT CONNECTOR MUST BE SEATED FLUSH ON PANEL APPEARS TO BE TILTED