Permit: T00EL01585
Permit Details
Apply Date:
06/23/2000
Applicant:
RALD CARL
Description:
UPGRADE:ELECTRIC 30 AMP TO 125 AMP
Contractors:
- E S C ELECTRIC INC ,
Completed Inspections
Permit Status: Final
Permit Number: T00EL01585
Permit Description: UPGRADE:ELECTRIC 30 AMP TO 125 AMP
Total Completed Inspections - 2
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/06/2000 | ELECTRIC - SERVICE UPGRADE | DSANTACR | Approved | IVRS - Inspection 0245* NOTES: INCREASE IS TO 200 AMP #4 BARE GROUND NOT #8 PERMANENT ADDRESS LABELS ON SERVICE 1 FOR EACH UNIT. GROUND SYSTEM WIRING MUST HAVE IRREVERSIBLE SPLICE IF USED. BOND GAS PIPING SYSTEM BOTH UNITS BOND WATER PIPING SYSTEM BOTH UNITS 2 GROUND RODS REQUIRED DUPLEX REQUIRES L-N LICENSE #? |
| 08/31/2000 | ELECTRIC - FINAL | RMAJUTA | Approved | NEED ENGRAVED OR RAISED LETTER METAL TAG FOR ADDRESS SCREWED OR TO SERVICE OLD DISCONNECT WILL NOT BE ALLOWED AS JUNCTION BOX WILL NEED APPROVED RAINTIGHT JUNCTION BOX WHEN READY FOR FINAL NEED NAME AND NUMBER OF C-11 ELECTRICAL CONTRACTOR |