Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
01/17/2001 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*
07/06/2000 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0245*
NOTES: INCREASE IS TO 200 AMP #4 BARE GROUND NOT #8
PERMANENT ADDRESS LABELS ON SERVICE 1 FOR EACH UNIT.
GROUND SYSTEM WIRING MUST HAVE IRREVERSIBLE SPLICE IF USED.
BOND GAS PIPING SYSTEM BOTH UNITS
BOND WATER PIPING SYSTEM BOTH UNITS
2 GROUND RODS REQUIRED
DUPLEX REQUIRES L-N LICENSE #?