Permit: T00EL00839
Permit Details
Apply Date:
04/03/2000
Applicant:
SCOTT CAROL-BALDRIDGE
Description:
UPGRADE:ELECTRIC 40 AMP TO 200 AMP
Outstanding Inspections
Permit Status: Expired
Permit Number: T00EL00839
Permite Description: UPGRADE:ELECTRIC 40 AMP TO 200 AMP
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/17/2000 | ELECTRIC - SERVICE UPGRADE | N/A | Correction Required | ADDTL COMMS - 1. METER CANNOT BE HIGHER THAN 6 3 TO CENTER 2. REMOVE FLOODS NEXT TO SERVICE MAST 3. INSTALL 2 GROUND ROD 5/8 X 8 AT LEAST 6 APART 4. INSTALL #4 WATER BOND 5. INSTALL #4 GAS BOND |
| 04/18/2000 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection 0999* |