Inspection Status: Correction Required
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 04/17/2000 |
ELECTRIC - SERVICE UPGRADE |
|
Correction Required |
ADDTL COMMS - 1. METER CANNOT BE HIGHER THAN 6 3 TO CENTER 2. REMOVE FLOODS NEXT TO SERVICE MAST 3. INSTALL 2 GROUND ROD 5/8 X 8 AT LEAST 6 APART 4. INSTALL #4 WATER BOND 5. INSTALL #4 GAS BOND |
| 04/17/2000 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999* |