Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address NEW:
4042 E CALLE DE JARDIN
Apply Date:
03/09/2000
Applicant:
WEBER CHARLES WALTER & MARYLOU J
Description:
UPGRADE:ELECTRIC TO 200 AMP

Outstanding Inspections

Permit Status: Expired
Permit Number: T00EL00594
Permite Description: UPGRADE:ELECTRIC TO 200 AMP
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
05/03/2000 ELECTRIC - SERVICE UPGRADE N/A Correction Required ADDTL COMMS - OK TO CLEAR
05/16/2000 ELECTRIC - FINAL N/A Correction Required ADDTL COMMS - (NEED ACCESS TO GAS BOND CONNECTION) 1. LIQUIDTIGHT FLEXIBLE NON METALIC CONDUIT SHALL NOT BE USED WHERE SUBJECT TO PHYSICAL DAMAGE PER N.E.C. ART 351-23 (B)-(C). 2. GROUNDING CONDUCTOR NEEDS TO BE PROPERLY TERMINATED USING AN APPROVED METHOD SUCH AS GROUNDING SCREW, GROUNDING LUG PROPERLY ATTACHED TO J-BOX (PER ART. 250 & 90-4&110-3 3. EQUIP GROUNDING CONDUCTOR AT 6X6X4 J-BOX MUST BE AT LEAST A #10 FOR 60 AMP CIRCUIT PER 250-122 N.E.C. 4. CONDUIT TO BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER PER 110-12 YOUR CONDUIT INSTALLATION IS WAY OUT OF PLUMB INSTALL USING A LEVEL OR GOOD EYE.