Permit: T00EL00594

Parcel: 126162670

Inspection Status: Correction Required

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/16/2000 ELECTRIC - FINAL Correction Required ADDTL COMMS - (NEED ACCESS TO GAS BOND CONNECTION) 1. LIQUIDTIGHT FLEXIBLE NON METALIC CONDUIT SHALL NOT BE USED WHERE SUBJECT TO PHYSICAL DAMAGE PER N.E.C. ART 351-23 (B)-(C). 2. GROUNDING CONDUCTOR NEEDS TO BE PROPERLY TERMINATED USING AN APPROVED METHOD SUCH AS GROUNDING SCREW, GROUNDING LUG PROPERLY ATTACHED TO J-BOX (PER ART. 250 & 90-4&110-3 3. EQUIP GROUNDING CONDUCTOR AT 6X6X4 J-BOX MUST BE AT LEAST A #10 FOR 60 AMP CIRCUIT PER 250-122 N.E.C. 4. CONDUIT TO BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER PER 110-12 YOUR CONDUIT INSTALLATION IS WAY OUT OF PLUMB INSTALL USING A LEVEL OR GOOD EYE.
05/16/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0999*