Inspection Status: Correction Required
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/16/2000 |
ELECTRIC - FINAL |
|
Correction Required |
ADDTL COMMS - (NEED ACCESS TO GAS BOND CONNECTION) 1. LIQUIDTIGHT FLEXIBLE NON METALIC CONDUIT SHALL NOT BE USED WHERE SUBJECT TO PHYSICAL DAMAGE PER N.E.C. ART 351-23 (B)-(C). 2. GROUNDING CONDUCTOR NEEDS TO BE PROPERLY TERMINATED USING AN APPROVED METHOD SUCH AS GROUNDING SCREW, GROUNDING LUG PROPERLY ATTACHED TO J-BOX (PER ART. 250 & 90-4&110-3 3. EQUIP GROUNDING CONDUCTOR AT 6X6X4 J-BOX MUST BE AT LEAST A #10 FOR 60 AMP CIRCUIT PER 250-122 N.E.C. 4. CONDUIT TO BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER PER 110-12 YOUR CONDUIT INSTALLATION IS WAY OUT OF PLUMB INSTALL USING A LEVEL OR GOOD EYE. |
| 05/16/2000 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999* |