Permit: T00EL00548
Permit Details
Apply Date:
03/06/2000
Applicant:
CANEZ JESSE C & CECELIA M JT/RS
Description:
SERVICE:RELOCATE
Outstanding Inspections
Permit Status: Expired
Permit Number: T00EL00548
Permite Description: SERVICE:RELOCATE
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/29/2000 | ELECTRIC - SERVICE UPGRADE | N/A | Correction Required | ADDTL COMMS - 1. USE PROPER CONNECTOR FOR GROUNDING CONDUCTORS AT J-BOXES PER 110-3 N.E.C. 2. USE N.M. CONNECTOR WHERE N.M. ENTERS PANELS PER 110-3 N.E.C. 3. MAKE UP ALL NEUTRALS (AT SWITCH BOXES) PER 90-4 N.E.C. 4. INSTALL TO AMP MAX BREAKER FOR EXISTING SUB-PANEL FEED PER ART 310-16 5. INSTALL #4 WATER BOND AND #4 GAS BOND PER N.E.C. ART 250 6. BRACE RISER ABOVE ROOF PER N.E.C.-230 AND T.E.P. 7. LABEL ADDRESS PER T.E.P. 8. INSTALL MISSING DEADFRONT COVER |
| 04/06/2000 | ELECTRIC - FINAL | N/A | Partial Approval | IVRS - Inspection 0000* |