Permit: T00EL00548

Parcel: 129063490


Addresses:

2520 E BEVERLY DR

Inspection Status: Correction Required

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
03/29/2000 ELECTRIC - SERVICE UPGRADE Correction Required ADDTL COMMS - 1. USE PROPER CONNECTOR FOR GROUNDING CONDUCTORS AT J-BOXES PER 110-3 N.E.C. 2. USE N.M. CONNECTOR WHERE N.M. ENTERS PANELS PER 110-3 N.E.C. 3. MAKE UP ALL NEUTRALS (AT SWITCH BOXES) PER 90-4 N.E.C. 4. INSTALL TO AMP MAX BREAKER FOR EXISTING SUB-PANEL FEED PER ART 310-16 5. INSTALL #4 WATER BOND AND #4 GAS BOND PER N.E.C. ART 250 6. BRACE RISER ABOVE ROOF PER N.E.C.-230 AND T.E.P. 7. LABEL ADDRESS PER T.E.P. 8. INSTALL MISSING DEADFRONT COVER
03/29/2000 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection 0000*