Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Address NEW:
1004 W CONGRESS ST
Apply Date:
02/14/2000
Applicant:
RESCON BERTHA
Description:
RECONNECT:ELECTRIC:OFFICE

Outstanding Inspections

Permit Status: Expired
Permit Number: T00EL00397
Permite Description: RECONNECT:ELECTRIC:OFFICE
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
02/16/2000 ELECTRIC - RECONNECT N/A Correction Required ADDTL COMMS - 1. INSTALL LIGHT FIXTURE IN HALL (MISSING) 2. PANEL IS REQUIRED TO HAVE CLEARANCE IN FRONT OF IT 30 WIDE, 36 OUT IN FRONT-SHELVES IN FRINGE ON THIS CLEARANCE THEY WILL HAVE TO BE MOVED. 3. NEUTRALS AND GROUNDS ARE NOT SUPPOSED TO BE TIED TOGETHER 4. INSTALL PANEL COVER 5. ROMEX HAS TO BE PHYSICALLY PROTECTED AND DEVICES COVERED 6. FEED FROM SERVICE DOES NOT FEED PANEL IN SPACE CANNOT LOCATE J-BOX. OBTAIN A GENERAL REPAIR PERMIT FOR MOVING WALLS IF YOU ARE DOIN SO.
02/18/2000 ELECTRIC - FINAL N/A Not ready for Inspection NOT READY FOR INSPECTION