Permit: T00EL00397
Permit Details
Apply Date:
02/14/2000
Applicant:
RESCON BERTHA
Description:
RECONNECT:ELECTRIC:OFFICE
Outstanding Inspections
Permit Status: Expired
Permit Number: T00EL00397
Permite Description: RECONNECT:ELECTRIC:OFFICE
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/16/2000 | ELECTRIC - RECONNECT | N/A | Correction Required | ADDTL COMMS - 1. INSTALL LIGHT FIXTURE IN HALL (MISSING) 2. PANEL IS REQUIRED TO HAVE CLEARANCE IN FRONT OF IT 30 WIDE, 36 OUT IN FRONT-SHELVES IN FRINGE ON THIS CLEARANCE THEY WILL HAVE TO BE MOVED. 3. NEUTRALS AND GROUNDS ARE NOT SUPPOSED TO BE TIED TOGETHER 4. INSTALL PANEL COVER 5. ROMEX HAS TO BE PHYSICALLY PROTECTED AND DEVICES COVERED 6. FEED FROM SERVICE DOES NOT FEED PANEL IN SPACE CANNOT LOCATE J-BOX. OBTAIN A GENERAL REPAIR PERMIT FOR MOVING WALLS IF YOU ARE DOIN SO. |
| 02/18/2000 | ELECTRIC - FINAL | N/A | Not ready for Inspection | NOT READY FOR INSPECTION |