Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Address NEW:
4995 N CASA GRANDE HY
Apply Date:
09/22/2000
Applicant:
KENNEDY JIM
Description:
CELL SITE
Contractors:
  • GRAY COMMUNICATION SERVICES

Permit Reviews

Permit Number - T00CM04728
Permit Status: Final
Permit Description: CELL SITE
Start Date Submittal Complete Date Status  
09/22/2000 CELL TOWER/ANTENNAS 12/18/2000 COMPLETED Review Details

Completed Inspections

Permit Status: Final
Permit Number: T00CM04728
Permit Description: CELL SITE
Total Completed Inspections - 8
Date Description Inspector Results Comments
11/21/2000 ELECTRIC - UNDERGROUND RHOLLAND Approved IVRS - Inspection 0000*
ONLY UNDERGROUND ON SITE AT THIS TIME IS UTILITY CONDUITS. THEY MEET CODE REQUIREMENTS
12/21/2000 ELECTRIC - FINAL RHOLLAND Approved IVRS - Inspection 0999*
GROUND RING SHOWS 2' FROM BUILIDNG ON PLANS ONLY 6" FROM BUILIDNG IN GROUND
PLANS SHOW AND SPECIFY 200 AP PLUG FOR GENERATOR PROVIDE REVISED PLANS OR INSTALL AS PER PLANS
NEED REJECTION CLIPS AT DISCONNECT
VERIFY TR 200R FUSES EQUAL TO LPN 200 AS PLANS
NEED LABELS AS PER PLAN
12/28/2000 ELECTRIC - UFER RHOLLAND Approved IVRS - Inspection 0000*
LETTER RECEIVED FROM M-3 REGARDING UFFER DISTANCE FROM BUILDING
01/04/2001 PERMIT FINALED EMONAHAN Approved
01/04/2001 BUILDING PRE-SLAB EMONAHAN Approved
01/05/2001 ELECTRIC - CABLE DROP RHOLLAND Approved IVRS - Inspection 0000*
01/05/2001 BUILDING - FINAL EMONAHAN Approved NEED TIE DOWN ANCHORS TO BE INSTALL
01/07/2001 ELECTRIC - TEMPORARY SERVICE RHOLLAND Approved

Documents

File Name Document Type  
STRUCCALC.TIF DOCUMENTS VIEW
None DOCUMENTS VIEW