Permit: T00CM04728
Permit Details
Status:
Final
Type:
COMMERCIAL OTHER
Address:
4995 N CASA GRANDE HY
Address NEW:
4995 N CASA GRANDE HY
Apply Date:
09/22/2000
Applicant:
KENNEDY JIM
Description:
CELL SITE
Contractors:
- GRAY COMMUNICATION SERVICES
Permit Reviews
Permit Number - T00CM04728
Permit Status: Final
Permit Description: CELL SITE
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 09/22/2000 | CELL TOWER/ANTENNAS | 12/18/2000 | COMPLETED |
Completed Inspections
Permit Status: Final
Permit Number: T00CM04728
Permit Description: CELL SITE
Total Completed Inspections - 8
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/21/2000 | ELECTRIC - UNDERGROUND | RHOLLAND | Approved | IVRS - Inspection 0000* ONLY UNDERGROUND ON SITE AT THIS TIME IS UTILITY CONDUITS. THEY MEET CODE REQUIREMENTS |
| 12/21/2000 | ELECTRIC - FINAL | RHOLLAND | Approved | IVRS - Inspection 0999* GROUND RING SHOWS 2' FROM BUILIDNG ON PLANS ONLY 6" FROM BUILIDNG IN GROUND PLANS SHOW AND SPECIFY 200 AP PLUG FOR GENERATOR PROVIDE REVISED PLANS OR INSTALL AS PER PLANS NEED REJECTION CLIPS AT DISCONNECT VERIFY TR 200R FUSES EQUAL TO LPN 200 AS PLANS NEED LABELS AS PER PLAN |
| 12/28/2000 | ELECTRIC - UFER | RHOLLAND | Approved | IVRS - Inspection 0000* LETTER RECEIVED FROM M-3 REGARDING UFFER DISTANCE FROM BUILDING |
| 01/04/2001 | PERMIT FINALED | EMONAHAN | Approved | |
| 01/04/2001 | BUILDING PRE-SLAB | EMONAHAN | Approved | |
| 01/05/2001 | ELECTRIC - CABLE DROP | RHOLLAND | Approved | IVRS - Inspection 0000* |
| 01/05/2001 | BUILDING - FINAL | EMONAHAN | Approved | NEED TIE DOWN ANCHORS TO BE INSTALL |
| 01/07/2001 | ELECTRIC - TEMPORARY SERVICE | RHOLLAND | Approved |