Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T00CM04728

Parcel: 10120032C

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/07/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
FINAL OK
CALLED VERONICA
01/04/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
GENERATOR PLUG NOT FULLY ATTACHED
MISSING BOTTOM LOCK NUT ON NIPPLE
NEED BUILDING DEVICE ON NIPPLE
01/02/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0920*
LOCKED NO ACCESS
12/21/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
GROUND RING SHOWS 2' FROM BUILIDNG ON PLANS ONLY 6" FROM BUILIDNG IN GROUND
PLANS SHOW AND SPECIFY 200 AP PLUG FOR GENERATOR PROVIDE REVISED PLANS OR INSTALL AS PER PLANS
NEED REJECTION CLIPS AT DISCONNECT
VERIFY TR 200R FUSES EQUAL TO LPN 200 AS PLANS
NEED LABELS AS PER PLAN
12/18/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
UFFER COVERED NO INSPECTION
NEED APPROVED SET OF PLANS ON SITE