Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/07/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* FINAL OK CALLED VERONICA |
|
| 01/04/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* GENERATOR PLUG NOT FULLY ATTACHED MISSING BOTTOM LOCK NUT ON NIPPLE NEED BUILDING DEVICE ON NIPPLE |
|
| 01/02/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0920* LOCKED NO ACCESS |
|
| 12/21/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* GROUND RING SHOWS 2' FROM BUILIDNG ON PLANS ONLY 6" FROM BUILIDNG IN GROUND PLANS SHOW AND SPECIFY 200 AP PLUG FOR GENERATOR PROVIDE REVISED PLANS OR INSTALL AS PER PLANS NEED REJECTION CLIPS AT DISCONNECT VERIFY TR 200R FUSES EQUAL TO LPN 200 AS PLANS NEED LABELS AS PER PLAN |
|
| 12/18/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* UFFER COVERED NO INSPECTION NEED APPROVED SET OF PLANS ON SITE |