Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
3211 E LEE ST
Address NEW:
3211 E LEE ST
Apply Date:
08/28/2000
Applicant:
TERILL SUSAN
Description:
AIR COND

Permit Reviews

Permit Number - T00CM04279
Permit Status: Expired
Permit Description: AIR COND
Start Date Submittal Complete Date Status  
08/28/2000 RESIDENTIAL BLDG/ZONING/FLOOD 08/30/2000 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T00CM04279
Permit Status: Expired
Permit Description: AIR COND
Total Outstanding Activity Conditions - 1
Date Name
08/28/2000 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T00CM04279
Permite Description: AIR COND
Total Outstanding Inspections - 4
Last Inspection Date Description Inspector Results Comments
ELECTRIC - INTERMEDIATE N/A Not Inspected
ELECTRIC - FINAL N/A Not Inspected
MECHANICAL - INTERMEDIATE N/A Not Inspected
09/07/2000 MECHANICAL - FINAL N/A Denied IVRS - Inspection 0999*
1. A/C ON SOUTH END- MUST HAVE ADEQUATE RETURN AIR WITH AN AIR FILTER. CANNOT DRAW RETURN AIR FROM THE KITCHEN
SEWER VENT NEAR COOLER MUST BE 10' AWAY OR 1' ABOVE
CONDENSATE DRAIN LINE CANNOT TERMINATE INTO ANY WASTE VENT SMALLER THAN 2" PVC MUST BE PAINTED WITH LATEX PAINT IF EXPOSED TO SUN BLOCK EVERY 4'
MUST HAVE DAMPER ON A/C UNIT TO PREVENT AIR FROM COOLER BLOWING THROUGH THE A/C UNIT
MUST USE A MIDWEST BOX FROM COOLER RECEPTACLES
BLOCK AND STRAP GAS LINES
LABEL CIRCUIT BREAKER
A/C ON NORTH END
BLOCK GAS LINE
USE APPROVED FITTINGS ON ELECTRICAL CONNECTIONS TO SWAMP COOLER
PAINT PVC W/LATEX PAINT CANNOT TERMINATE INTO WASTE VENTS SWALLER THAN 2" BLOCK EVERY 4'
NO BACK DRAFT DAMPER AT A/C UNIT
LABEL CIRCUIT BREAKERS