3211 E LEE ST

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
03/08/2001 MECHANICAL - FINAL Denied IVRS - Inspection 0999*1) NO CORRECTIONS HAVE BEEN MADE 2) CORRECTIONS TO THE SYSTEM ARE NECESSARY AS THIS IS GOING TO BE AN INEFFICENT SYSTEM TO OPERATE. PLEASE CALL ME AND LET ME KNOW WHO YOUR MECH CONTRACTOR IS SO THAT THESE CORRECTIONS CAN BE MADE
09/07/2000 MECHANICAL - FINAL Denied IVRS - Inspection 0999*
1. A/C ON SOUTH END- MUST HAVE ADEQUATE RETURN AIR WITH AN AIR FILTER. CANNOT DRAW RETURN AIR FROM THE KITCHEN
SEWER VENT NEAR COOLER MUST BE 10' AWAY OR 1' ABOVE
CONDENSATE DRAIN LINE CANNOT TERMINATE INTO ANY WASTE VENT SMALLER THAN 2" PVC MUST BE PAINTED WITH LATEX PAINT IF EXPOSED TO SUN BLOCK EVERY 4'
MUST HAVE DAMPER ON A/C UNIT TO PREVENT AIR FROM COOLER BLOWING THROUGH THE A/C UNIT
MUST USE A MIDWEST BOX FROM COOLER RECEPTACLES
BLOCK AND STRAP GAS LINES
LABEL CIRCUIT BREAKER
A/C ON NORTH END
BLOCK GAS LINE
USE APPROVED FITTINGS ON ELECTRICAL CONNECTIONS TO SWAMP COOLER
PAINT PVC W/LATEX PAINT CANNOT TERMINATE INTO WASTE VENTS SWALLER THAN 2" BLOCK EVERY 4'
NO BACK DRAFT DAMPER AT A/C UNIT
LABEL CIRCUIT BREAKERS