Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/08/2001 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*1) NO CORRECTIONS HAVE BEEN MADE 2) CORRECTIONS TO THE SYSTEM ARE NECESSARY AS THIS IS GOING TO BE AN INEFFICENT SYSTEM TO OPERATE. PLEASE CALL ME AND LET ME KNOW WHO YOUR MECH CONTRACTOR IS SO THAT THESE CORRECTIONS CAN BE MADE | |
| 09/07/2000 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* 1. A/C ON SOUTH END- MUST HAVE ADEQUATE RETURN AIR WITH AN AIR FILTER. CANNOT DRAW RETURN AIR FROM THE KITCHEN SEWER VENT NEAR COOLER MUST BE 10' AWAY OR 1' ABOVE CONDENSATE DRAIN LINE CANNOT TERMINATE INTO ANY WASTE VENT SMALLER THAN 2" PVC MUST BE PAINTED WITH LATEX PAINT IF EXPOSED TO SUN BLOCK EVERY 4' MUST HAVE DAMPER ON A/C UNIT TO PREVENT AIR FROM COOLER BLOWING THROUGH THE A/C UNIT MUST USE A MIDWEST BOX FROM COOLER RECEPTACLES BLOCK AND STRAP GAS LINES LABEL CIRCUIT BREAKER A/C ON NORTH END BLOCK GAS LINE USE APPROVED FITTINGS ON ELECTRICAL CONNECTIONS TO SWAMP COOLER PAINT PVC W/LATEX PAINT CANNOT TERMINATE INTO WASTE VENTS SWALLER THAN 2" BLOCK EVERY 4' NO BACK DRAFT DAMPER AT A/C UNIT LABEL CIRCUIT BREAKERS |