Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
C of o
Type:
COMMERCIAL ALTERATION
Address:
5740 E 22ND ST
Address NEW:
5740 E 22ND ST
Apply Date:
08/04/2000
Applicant:
VENEZIANO, PHILIP JOHN
Description:
TI:OFFICE
Architects:
  • VENEZIANO, PHILIP JOHN
Contractors:
  • AXIOM BUILDERS INC ,

Permit Reviews

Permit Number - T00CM03879
Permit Status: C of o
Permit Description: TI:OFFICE
Start Date Submittal Complete Date Status  
08/04/2000 COMMERCIAL TI 02/09/2001 COMPLETED Review Details
10/13/2000 REVISION 02/09/2001 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T00CM03879
Permit Status: C of o
Permit Description: TI:OFFICE
Total Outstanding Activity Conditions - 1
Date Name
08/04/2000 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T00CM03879
Permit Description: TI:OFFICE
Total Completed Inspections - 11
Date Description Inspector Results Comments
09/27/2000 MECHANICAL - INTERMEDIATE JMILITEL Approved IVRS - Inspection 0000*
10/13/2000 MECHANICAL - PROGRESS JMILITEL Approved IVRS - Inspection 0000*
10/13/2000 MECHANICAL - ABOVE CEILING JMILITEL Approved OK TO CLOSE CEILING
10/30/2000 ELECTRIC - UNDERGROUND MCAPISTR Approved IVRS - Inspection 0000*
11/06/2000 SHEET ROCK NAILING DWITT Approved IVRS - Inspection 0000*
RE SCREW WHERE SCREWS ARE LESS THAN 3/8"FROM EDGE
RE SCREW WHERE PAPER IS BROKEN
11/17/2000 PLUMBING - GAS PRESSURE TEST JMILITEL Approved IVRS - Inspection 0000*
11/21/2000 ELECTRIC - ABOVE CEILING MCAPISTR Approved IVRS - Inspection 0000*
12/11/2000 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection 0999*
INSTALL OUTSIDE AIR VENTS ON A/C UNITS AS PER PLAN
INSTALL CONDENSATE DRAIN LINES CANNOT DRAIN ONTO CONCRETE OR PAVEMENT.
PAINT EXPOSED PVC W/LATEX PAINT NOT SPRAY ENAMEL.
#8 WIRE NOT ADEQUATE FOR 60 AMP. USE #6 TO A/C UNITS #3
A/C #2 NOT FUSED PROPERLY
PERMANENTLY LABEL UNITS (AC-1,AC-Z,ETC
CORRECT AND RECALL FOR FINAL
12/11/2000 ELECTRIC - FINAL MCAPISTR Approved IVRS - Inspection 0000*
12/11/2000 ELECTRIC - INTERMEDIATE MCAPISTR Approved
12/11/2000 BUILDING - FINAL DWITT Approved IVRS - Inspection 0000*