Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T00CM03879
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/01/2001 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* ALL CORRECTIONS HAVE BEEN MADE |
|
| 01/08/2001 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0935* STILL HAVE #8 WIRE ON 60 AMP CIRCUIT TO A/C EQUIPMENT PVC NOT PAINTED W/LATEX PAINT USE A ROOF JACK ON CONDENSATE DRAIN PENETRATION THROUGH ROOF BLOCK AND CLAMP DRAIN LINE UNIT #3 NEEDDS AN OUTSIDE AIR VENT PAY RE-INSPECTION FEE PRIOR TO NEX INSPECTION |
|
| 12/11/2000 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* INSTALL OUTSIDE AIR VENTS ON A/C UNITS AS PER PLAN INSTALL CONDENSATE DRAIN LINES CANNOT DRAIN ONTO CONCRETE OR PAVEMENT. PAINT EXPOSED PVC W/LATEX PAINT NOT SPRAY ENAMEL. #8 WIRE NOT ADEQUATE FOR 60 AMP. USE #6 TO A/C UNITS #3 A/C #2 NOT FUSED PROPERLY PERMANENTLY LABEL UNITS (AC-1,AC-Z,ETC CORRECT AND RECALL FOR FINAL |
|
| 11/21/2000 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* | |
| 10/13/2000 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection 0000* |