Permit: T00CM03120
Permit Details
Apply Date:
06/22/2000
Applicant:
SONORA EXPEDITING
Description:
TI:RETAIL
Architects:
- BLACK, MICHAEL RAY
Contractors:
- DAN KUYKENDALL ENTERPRISES INC
Permit Reviews
Permit Number - T00CM03120
Permit Status: Final
Permit Description: TI:RETAIL
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
07/31/2000 | REVISION - RESUBMITTAL | 08/02/2000 | COMPLETED |
08/07/2000 | REVISION - RESUBMITTAL | 08/16/2000 | COMPLETED |
Completed Inspections
Permit Status: Final
Permit Number: T00CM03120
Permit Description: TI:RETAIL
Total Completed Inspections - 1
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/24/2000 | ELECTRIC - ABOVE CEILING | RSUBA | Approved | IVRS - Inspection 0999* TRAC LIGHTING NEEDS SIESMIC SUPPORT J-BOXES OVERFILLED (SEE ART 370-6) CONDUIT AND J-BOXES CANNOT BE SECURED FROM THE GRID STRUCTURAL INSTALL SEPERATE SIESMIC WIRE FOR ELEC SUPPORT FINISH ALL MAKE UP OF J-BOXES WIRE STILL BEING PULLED ALONG WITH CONDUIT INSTALLATION SECURE ALL EMT WITHIN 3" OF J-BOXES (PER 248-13 N.E.C. FIELD COLLECTED AFTER HRS INSPECTION 98.50 FROM JOSEPH CLONTAN CHECK # 4719 |