Permit: T00CM02654
Permit Details
Status:
Expired
Type:
SINGLE FAMILY ALTERATION
Address:
3927 E MABEL ST
Address NEW:
3927 E MABEL ST
Apply Date:
05/23/2000
Applicant:
MEIJER JOHAN
Description:
ENCLOSE:GARAGE INTO ROOM T99VL02764
Permit Reviews
Permit Number - T00CM02654
Permit Status: Expired
Permit Description: ENCLOSE:GARAGE INTO ROOM T99VL02764
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 08/04/2000 | RESIDENTIAL BLDG/ZONING/FLOOD | 02/02/2001 | COMPLETED |
Outstanding Inspections
Permit Status: Expired
Permit Number: T00CM02654
Permite Description: ENCLOSE:GARAGE INTO ROOM T99VL02764
Total Outstanding Inspections - 4
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/06/2000 | BUILDING - FINAL | N/A | Denied | IVRS - Inspection 0950*/ 1. PROVIDE PROOF OF ELECT SUB PANEL GROUND. EXPOSE RODS. 2. INADEQUATE SEWER VENT--MUST HAVE EQUIVALENT OF 8" SEWER LINE IN VENT SYSTEM. 3. EXPOSE SEWER LINE FROM GARAGE TO SEWER CONNECTION. 4. INSTALL SEWER CLEAN OUT. (2 WAY). 5. GFCI ELECTRIC OUTLET REQUIRED ON 12" COUNTER RT OF RANGE. 6. INADEQUATE EGRESS FROM BEDROOM--WINDOW MUST COMPLY WITH UBC SECTION 310.4. 7. INADEQUATE CEILING HEIGHT IN LIVING ROOM. 7'-6" REQUIRED ACTUAL 7'-4". 8. EXPOSE RANGE OUTLET. 9. EXPOSE ELECTRIC UNDERGROUND CONDUIT. |
| 10/06/2000 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection 0950* |
| 10/06/2000 | PLUMBING - FINAL | N/A | Denied | IVRS - Inspection 0950* |
| 10/06/2000 | MECHANICAL - FINAL | N/A | Denied | IVRS - Inspection 0950* |