Permit: T00CM02463
Permit Details
Apply Date:
05/12/2000
Applicant:
FENECK, JOHN
Description:
TI:OFFICE
Architects:
- FENECK, JOHN
Contractors:
- DAVIS DESIGN AND CONSTRUCTION L
Completed Inspections
Permit Status: C of o
Permit Number: T00CM02463
Permit Description: TI:OFFICE
Total Completed Inspections - 1
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/31/2000 | ELECTRIC - INTERMEDIATE | RMAJUTA | Approved | ADDTL COMMS - 1. DISCONNECT FOR WH NOT INSTALLED NO 30 A CD PER PLAN 2. RECEPTACLE TO BE RAISED BY SINK NOT IN 3. NEW SERVICE ADDRESSED 215 PERMIT SHOWS 216? 4. INSTALL REJECT PINS IN DISCONNECT FOR R TYPE FUSES 5. LB ENTERING METER ENCLOSURE CANNOT USE BROKEN FITTING TO CONNECT LB NEED TO USE A GROUND BUSHING AT SERVICE EQUIPMENT AROUND CONCENTRIC OR EXCENTRIC KOS 6. SUPPORT SEAL TIGHT PER 99 NEC WITHIN 12 OF ENCLOSURE |